GE MULTILIN TM PMCS 6.15 Read-This-Book-First Installation Guide DEH-211 GE Power Management Control System

Strona 2

Introduction Welcome Hello and welcome to the POWER LEADER Power Management Control System for CIMPLICITY® HMI. You are about to begin using your comp

Strona 3

About CIMPLICITY PMCS Version 6.15 CIMPLICITY PMCS Version 6.15 is the latest Power Management Control System in the robust line of POWER LEADER powe

Strona 4

• CIMPLICITY PMCS Interface Toolkit with tools to quickly create accurate, intelligent floor plans, one-line diagrams, and elevation views. • System

Strona 5

(This page left blank intentionally) CIMPLICITY PMCS Read-This-Book-First Introduction • 9

Strona 6 - Contents

Getting Started First Steps If you are already familiar with PMCS, simply review the system requirements and skip ahead to Chapter 3. Getting started

Strona 7

Communication network: A physical standard for wiring and interconnection of communicating devices. A communication network standard usually includes

Strona 8

NetDDE: A version of Dynamic Data Exchange (DDE) that allows communications between applications running on different PCs over network connections. NT

Strona 9

System Requirements The following table shows the minimum and recommended PC system configuration for running PMCS Version 6.15. Note that regardles

Strona 10 - Introduction

PMCS 6.15 Envelope definition 1) Physical System Size • 75 power management devices (IEDs) (100 max), • 150 I/O points (through IEDs or PLC

Strona 11 - Features

Where to Get Help The GE Industrial Systems Resolution Center is available at 1-888-GE-RESOLV to answer your questions about installing or using PMC

Strona 12 - Supported Devices

Notice The information contained in this document is subject to change without notice. GE makes no warranty of any kind with regard to this material,

Strona 13

(This page left blank intentionally) 16 • Getting Started CIMPLICITY PMCS Read-This-Book-First

Strona 14 - Getting Started

Installing the Software Computer Preparation PMCS must be installed on a PC running Windows 2000 SP4. This host PC must be dedicated to the PMCS syst

Strona 15

When Installing On Windows 2003 Server The Following steps to be executed before starting the PMCS installation. This applies for all the licenses of

Strona 16

Click on Apply and then click on Ok button. After this restart the PC and then start the PMCS installation process as mentioned in this document. In

Strona 17 - System Requirements

Installing Additional Software Install any additional software, such as Microsoft Excel, at this point in the procedure. Follow the instruction proced

Strona 18 - 2) HMI Application Size

Select the appropriate network adapter from the list and click Have Disk…. Follow the instructions provided on the screen to complete the network ca

Strona 19 - What’s next?

Local Area Network (LAN) Interfaces PMCS supports multiple View Nodes through NetDDE links over a local area network. Thus, in addition to the PMCS n

Strona 20

Installing Additional Software Install any additional software, such as Microsoft Excel or COMTRADE file browsers for analyzing waveform files, at th

Strona 21 - Installing the Software

your eLicense Option screen (see below). This screen allows you to either trial or fully license your PMCS software. 720 Hours (30-Day) Trial

Strona 22

Selecting the Web License option from the License Option brings you to the Web License Screen. This screen requires you to enter your eLicense Order

Strona 23 - Installing CIMPLICITY

GE MULTILIN TM PMCS 6.15 Read-This-Book-First Microsoft, Microsoft Excel and Microsoft PowerPoint are registered trademarks, and Windows 2000 is a

Strona 24

2. When the system on which PMCS is being installed is not having any .Net Framework installed on it. The PMCS 6.15 installation will go ahead by ins

Strona 25

3. In the Run dialog box, enter X:\setup (where X is the appropriate CD-ROM drive designation). 4. The below screen is observed when .Net is not

Strona 26

28 • Installing the Software CIMPLICITY PMCS Read-This-Book-First

Strona 27 - Installing the PMCS software

5. Click on I agree and click on Install button. It will now install .Net Framework on the machine where PMCS installation is started. After the .

Strona 28 - Licensing via the Web

6. GE PMCS 6.15 welcome screen appears. When you select the Next button in the Welcome screen, the PMCS license agreement screen is shown. Please t

Strona 29 - PMCS Installation Steps

7. At the User Information screen shown below, enter your name, your company name, and the serial number for the PMCS component you are installing

Strona 30

When you select the Next button in the User Information screen, a registration confirmation screen prompts you to verify your entries. Ensure that y

Strona 31

At the Choose Destination Location dialog, specify a drive on which to install PMCS. Default is “C”. Click Next to continue. CIMPLICITY PMCS Read-Th

Strona 32

9. At the Setup Type screen, select Custom installation, standard PMCS installation, or PMCS with EPM 7700 Components. PMCS installation is recommend

Strona 33

10. If you did not select “PMCS with EPM 7700 Components” in the Setup Type dialog box (Step 9), skip this step and proceed to Step 13. If you are i

Strona 35

11. If you did not select “PMCS with EPM 7700 Components” in the Setup Type dialog box (Step 9) or if you selected “Primary Node Installation” in Ste

Strona 36

12. If you did not select “PMCS with EPM 7700 Components” in the Setup Type dialog box (Step 9), or if you selected “Primary Node Installation” in S

Strona 37

13. Select the Program Folder for PMCS installation. It is recommended that the default Program Folder be chosen. Click Next to continue. 38 • Ins

Strona 38

14. If you chose the “PMCS” installation, you may be presented with one DDE Server selections depending upon the PMCS catalog number you entered in

Strona 39

40 • Installing the Software CIMPLICITY PMCS Read-This-Book-First

Strona 40

16. The Selected Components screen offers you the opportunity to verify the installation settings before any files are copied to your hard drive. C

Strona 41

17. After completing the selected PMCS installation, the installation program checks the host PC for an older version of the POWER LEADER Modbus Moni

Strona 42

If No is selected and clicked on finish it will prompt the below message box and will again redirect to the above dialog asking to restart. So sele

Strona 43

. After PMCS IIS – Setting up PMCS Server For any PMCS remote viewer system to connect to the PMCS server, the prerequisite is to have IIS installed

Strona 44

In order to unlicense your software to use your eLicense Order ID for another computer – you must have an internet connection. To retrieve your licen

Strona 45

(This Page is Left Blank Intentionally) CIMPLICITY PMCS Read-This-Book-First • i

Strona 46

NOTE: The Uninstaller may not delete some files such as error logs, system logs, and configuration records, which are created after the PMCS installat

Strona 47

Reinstallation Steps Follow the procedure below to reinstall your PMCS software. 1. If your system includes the PMCS Interface Toolkit, uninstall th

Strona 48 - Un-elicensing PMCS

Upgrading from previous versions to PMCS 6.15 PMCS 6.15 provides an easy-to-use, automatic upgrade path from previous versions of PMCS. The software

Strona 49 - Uninstalling PMCS

WARNING: Event Logger users only: Upgrading your EventServer or Eventlogger application will result in the loss of all device configurations and ann

Strona 50

Working with Cimplicity Viewer Node How to view the screens on a viewer node To configure the project on a Cimplicity viewer node, running on a

Strona 51 - Reinstallation Steps

CIMPLICITY PMCS Read-This-Book-First • 51

Strona 52

Configuring the Software To get the most out of your new PMCS system, follow the directions below to configure your system. Organize Your Informati

Strona 53

Ethernet Gateway IP Address COM port Modbus RTU Address Device Type Device (Topic) Name 10.47.28.201 1 2 EPM 9650Q E9650Q 10.47.28.201 1 12 E3720

Strona 54

Configuration Procedure Follow the procedure below to efficiently configure your system and minimize your time to startup. Host PC Configuration 1. C

Strona 55

EPM Software Components Configuration The EPM 7700, EPM 7600 and EPM 7500 requires several separate software components which are installed during th

Strona 56 - Configuring the Software

Back to Main Page Contents Introduction 6 Welcome...

Strona 57 - View Node

(This page left blank intentionally) 56 • Configuring the Software CIMPLICITY PMCS Read-This-Book-First

Strona 58 - Configuration Procedure

EPM Device-Special Considerations Introduction The GE EPM 7700, EPM 7600 and EPM 7500 devices add new level of power management capabilities to PMCS.

Strona 59

EPM Software Components There are four major components of the EPM software. The Network Builder, ION Designer, Communications Server, and ION_LINK DD

Strona 60

Workstation Configuration Guidelines If you are using the EPM 7700, EPM 7600 or EPM 7500 Meters in your PMCS network, the following guidelines in thi

Strona 61 - Special Considerations

Configuring the EPM Device Network The PMCS installation routine described earlier in this manual creates initial workstation and software node entri

Strona 62 - EPM Software Components

Building the Power-Monitoring Network in NetBuilder When Network Builder is running, you can begin configuring your EPM system by adding a site to th

Strona 63

Adding Software Nodes Software nodes identify the various software components in the network. Stationless Secondary nodes, although they are physicall

Strona 64 - Running Network Builder

Adding an Ethernet Site An Ethernet site defines the network connection between the devices and the Workstation(s). You add Ethernet sites to Worksta

Strona 65 - NetBuilder

Set the following communications parameters for the site. • Enter the Transmit delay setting (in milliseconds). This setting determines the level o

Strona 66 - Adding Software Nodes

Adding Devices (Meters) To add a meter, right-click on the Ethernet site you want to add the meter to, and select Insert Device… from the pop-up menu

Strona 67 - Adding an Ethernet Site

Organize Your Information...52 Configuration Procedure ...

Strona 68

(This page left blank intentionally) 66 • EPM Device-Special Considerations CIMPLICITY PMCS Read-This-Book-First

Strona 69 - Saving and Exiting

Index A alarm, 4 D DDE Server, 54 E Ethernet, 4, 8, 18, 19, 48, 50 event, 4 F Fanuc, 4 First Steps, 7 I Interface Toolkit, 5, 8, 43, 50 M minimum sys

Strona 70

GE MULTILIN General Electric Company 215 Anderson Avenue, Markham ON, L6E 1B3,

Strona 72 - GE MULTILIN

(This page left blank intentionally) CIMPLICITY PMCS Read-This-Book-First Introduction • 5