Appendix C Soft Switch Parameters
Correct Results of Soft Switch Configuration
If the values displayed from the CHSOSW command are not correct, reenter the
command with the desired parameters. Enter the command SOSW to see the
current Soft Switch values.
If the Soft Switch LED pattern is displayed but no “sign-on message” or prompt
appears on the terminal, check the construction and connections of the serial cable
and verify that the terminal is operating at the 9600 bps data rate. The sign-on
message can be repeated by pressing the LAN Interface Restart button.