177
Exiting Failsafe
Failsafe Handling
7. Select the Clear Latch button.
8. Select Yes when the dialog box request a change to OOS.
Step Four
This step requires permission level 2, 3, 4, 8 or 9:
1. Open the Operation State dialog box.
2. Select Manual.
3. Select OK.
4. Enter the Actual Position value in the Set Point text box.
5. Select OK.
Step Five
This step requires permission level 3,4,8 or 9:
1. Open the Configuration dialog.
2. Select the Position tab.
3. Set the Tight Shutoff and Position Low Limit parameters to -10 lower than the Actual
Position recorded in Step 3.
4. Set the Time 2 parameter to -1 (Figure 161).
Figure 161 Resetting Failsafe Parameters
Before Normal Configuration
After getting Out of Failsafe Configuration